Reading the Device Data with DIGSI 5
Select the device in the project tree.
²
Double-click Device information in the project tree.
²
In the Device information tab, you can find the data on your SIPROTEC 5 device.
[scgerdia-230816-01, 1, en_US]
Figure 10-2
Click the Logs tab.
²
Read other logs such as the Device-diagnosis log.
²

Measures for Error Correction

10.2.2
Limit work on the hardware to the necessary extent.
NOTE
i
i
Defective modules can be replaced only by experienced persons. Never open modules yourself.
The following software measures are possible:
Initializing the system
If, for example, you would like to set a supervision function so that it becomes more insensitive since it is
responding sporadically in the operating state, change the parameterization.
NOTE
i
i
If these measures do not lead to the desired result, avoid further measures during operation.

Fallback Mode

10.2.3
If an error is detected in the device that cannot automatically be cleared (hardware components, software or
parameters), the device switches automatically into fallback mode. This can appear in system start or during
operation of the device. The fallback mode allows you a minimum procedure with error diagnosis and error
correction.
SIPROTEC 5, Operation, Manual
C53000-G5040-C003-C, Edition 08.2020
Reading Device Information
Maintenance, On-the-Spot Assistance and Test
10.2 Error Search and Correction