Maintenance, On-the-Spot Assistance and Test

10.5 Test and Diagnostics

10.5
Test and Diagnostics

Establishing Test Mode

10.5.1
Safety Instructions
!
DANGER
Danger due to the execution of test functions
Noncompliance with safety instructions will result in death, serious injury, or significant material
damage.
The execution of test functions requires a high degree of qualification and precise know-how of
²
system conditions.
Procedure
DIGSI 5 offers the possibility to start different test and diagnostic functions for a SIPROTEC 5 device in the
Online operating mode. Chapter
the device together with DIGSI 5.
Activate the test functions using the menu bar and the different functions that you can reach via the list view
of the device.
Open the device in Online operating mode.
²
Open Test suite in the project tree.
²
[sc_tstsut-040718, 1, en_US]
Figure 10-22
All subordinate test options appear in the data window. Select the desired test editor and start the test. If
configured, enter the confirmation ID. In some test functions the device switches to an operating mode that
first requires a system start of the device. Confirm this with DIGSI 5. The selected test function is then avail-
able.
256
9.2.1 Test Functions
Test Suite
contains a description of the test functions offered by
C53000-G5040-C003-C, Edition 08.2020
SIPROTEC 5, Operation, Manual