3
ANALOG OUTPUT MODULE REPLACEMENT
Between the I/O terminal and programmable controller power supply:
photocoupler isolation
Between output channels: non-isolation
Between external power supply and analog output: transformer isolation
Between the I/O terminal and programmable controller power supply:
500VAC, for 1 minute
Between the I/O terminal and programmable controller power supply:
500VDC, 20M or more
(I/O assignment: intelligent 16 points)
18-point terminal block
(Sleeved solderless terminal cannot be used.)
24VDC +20%, -15%
Ripple, spike 500mV
2.5A, 250µs or less
Q62DAN
16 points
2
0.3 to 0.75mm
R1.25-3
0.33A
or less
P-P
0.15A
0.19kg
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Precautions for replacement
The number of occupied I/O points
has changed to 16 points.
×
×
Wiring change is required.
×