POSITIONING MODULE REPLACEMENT
Model
AD75M1
Item
I/O points
No. of module occupied slots
Weight
START signal
I/O signal for
external
devices
CHG signal
Connection
with peripheral
devices
peripheral
devices (data
setting, etc.)
AD75TU
GX
Configurator
*1
Nos.1 to 100 data items/axis of positioning data can be set using the buffer memory and Nos.1 to 600 data/axis can be set
with QD75M.
The positioning data in the buffer memory is not backed up.
*2
The near pass function is valid only during the continuous path control. (AD75M: Selected with parameters, QD75M:
Standard function)
QD75M does not have address pass mode. If passing the positioning address, continue with continuous operation.
(However, it will stop once.)
*3
GX Configurator-QP is available with SW2D5C-QD75P or later version.
7
- 23
AD75M2
AD75M3
32 points
(I/O assignment: special 32 points)
1
0.35kg
Speed-position switching signal
Direct connection
Available
GX Configurator-AP
: Compatible,
QD75M1
QD75M2
QD75M4
32 points
(I/O assignment: intelligent 32 points)
1
0.15kg
0.15kg
0.16kg
× (integrated into CHG)
External command signal (External start or
speed-position switching selectable with
parameters)
Connection via programmable controller
CPU, Q corresponding serial
communication module, Q corresponding
MELSECNET/H remote I/O module
Unavailable
*3
GX Configurator-QP
: Partial change required, ×: Incompatible
Compati-
Precautions for
bility
replacement
When using both the
speed-position
switching control and
the external start, input
the external start signal
to the interrupt module
and start using the
direct output.
The connecting shape
differs.
AD75TU cannot be
used.
×
Use GX Configurator-
QP.
Available GX
Configurator differs.