3
ANALOG OUTPUT MODULE REPLACEMENT
16-bit signed binary
(Normal resolution mode: -4096 to 4095,
High resolution mode: -12288 to 12287)
(External load resistance value: 0 to 600)
Normal resolution mode
Analog output
Digital input
range
0 to 20mA
4 to 20mA
Current
User range
settings
Ambient temperature 25±5°C: within ±0.1% (±20µA)
Ambient temperature 0 to 55°C: within ±0.3% (±60µA)
Max. 100,000 times
Q68DAIN
0 to 20mADC
High resolution mode
Maximum
Digital input
value
resolution
value
5µA
0 to 4000
0 to 12000
4µA
-4000 to
-12000 to
1.5µA
4000
12000
-
80µs/channel
21mA
8 channels/module
Available
: Compatible,
Compatibility
Maximum
resolution
1.66µA
1.33µA
0.83µA
: Partial change required, ×: Incompatible