Mitsubishi Electric MELSEC-A/QnA Series Handbook page 137

Table of Contents

Advertisement

3
ANALOG OUTPUT MODULE REPLACEMENT
(Normal resolution mode: -4096 to 4095,
High resolution mode: -12288 to 12287, -16384 to 16383)
-10 to 10VDC (External load resistance value: 1k to 1M)
Normal resolution mode
Analog output
Digital input
range
value
0 to 5V
0 to 4000
1 to 5V
Voltage
-10 to 10V
-4000 to 4000
User range
settings
Ambient temperature 25±5°C: within ±0.1% (±10mV)
Ambient temperature 0 to 55°C: within ±0.3% (±30mV)
Between the I/O terminal and programmable controller power supply:
Between output channels: non-isolation
Between external power supply and analog output: transformer isolation
Between the I/O terminal and programmable controller power supply:
Between the I/O terminal and programmable controller power supply:
500VDC, 20M or more
(I/O assignment: intelligent 16 points)
FG terminal: R1.25-3, 1.25-YS3, RAV1.25-3, V1.25-YS3A
Terminals other than FG: R1.25-3
(Sleeved solderless terminal cannot be used.)
Q68DAVN
16-bit signed binary
High resolution mode
Maximum
Digital input
resolution
value
1.25mV
0 to 12000
1.0mV
2.5mV
-16000 to 16000
0.75mV
-12000 to 12000
80µs/channel
±12V
8 channels/module
Max. 100,000 times
Available
photocoupler isolation
500VAC, for 1 minute
16 points
18-point terminal block
2
0.3 to 0.75mm
0.38A
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Maximum
resolution
0.416mV
0.333mV
0.625mV
0.333mV
The number of occupied I/O points
has changed to 16 points.
×
×
Wiring change is required.
×
The recalculation of internal current
consumption (5VDC) is required.
Precautions for replacement
3
- 60