Buffer Memory Address Comparison - Mitsubishi Electric MELSEC-A/QnA Series Handbook

Table of Contents

Advertisement

4
TEMPERATURE INPUT MODULE REPLACEMENT

4.2.4 Buffer memory address comparison

Sequence program change is required as the assignment of buffer memory differs.
For details of buffer memories and sequence programs, refer to the Thermocouple Input Module/
Channel Isolated Thermocouple/Micro Voltage Input Module User's Manual.
A616TD
Address
Name
(hex)
00
Data format selection
01
Error code storage
Error occurrence A60MXCONNECT No.
02
storage
Thermocouple type setting error channel
03
number storage
04
Current sampling period storage
05 to 0E
System area (Not used)
0F
Conversion enable/
10 to 17
disable specification
18
Setting data set request
19 to 1F
System area (Not used)
Disconnection detection enable/disable
20 to 27
specification
28 to 2F
System area (Not used)
30 to 3F
Digital output value temperature setting
Disconnection detection channel number
40 to 47
storage
48 to 4F
System area (Not used)
Digital output value out-of-range
50 to 57
Channel number storage
58 to 5F
System area (Not used)
Detected temperature value out-of-range
60 to 67
Channel number storage
68 to 6F
System area (Not used)
INPUT channel
70 to 7F
Digital output value storage
80 to FF
Error correction value setting
100 to 17F Thermocouple type setting
MX CH.channel
180 to 1FF
Digital output value storage
MX CH.channel
200 to 27F
Detected temperature value storage
4
- 9
Read/write
R/W
R
-
A616TD
Multiplexer module
R/W
-
R/W
-
R/W
-
R/W
-
R/W
-
R
R/W
R
Q64TD
Address
Name
(hex)
00
Conversion enable/disable setting
01
CH1 Time/count averaging setting
02
CH2 Time/count averaging setting
03
CH3 Time/count averaging setting
04
CH4 Time/count averaging setting
05 to 08
System area (Not used)
09
Averaging processing selection
0A
Conversion completion flag
0B
CH1 Measured temperature value
0C
CH2 Measured temperature value
0D
CH3 Measured temperature value
0E
CH4 Measured temperature value
0F to 12
System area (Not used)
13
Error code
14
Setting range
15 to 2E
System area (Not used)
2F
Warning output enable/disable setting
30
Warning output flag
31
Disconnection detection flag
32
CH1 Scaling value
33
CH2 Scaling value
34
CH3 Scaling value
35
CH4 Scaling value
36 to 3D System area (Not used)
3E
CH1 Scaling range lower limit value
3F
CH1 Scaling range upper limit value
40
CH2 Scaling range lower limit value
41
CH2 Scaling range upper limit value
42
CH3 Scaling range lower limit value
43
CH3 Scaling range upper limit value
44
CH4 Scaling range lower limit value
45
CH4 Scaling range upper limit value
46 to 4D System area (Not used)
4E
CH1 Scaling width lower limit value
4F
CH1 Scaling width upper limit value
50
CH2 Scaling width lower limit value
51
CH2 Scaling width upper limit value
52
CH3 Scaling width lower limit value
53
CH3 Scaling width upper limit value
54
CH4 Scaling width lower limit value
55
CH4 Scaling width upper limit value
56
CH1 Warning output lower/lower limit value
57
CH1 Warning output lower/upper limit value
Read/write
R/W
-
R/W
R
-
R
-
R/W
R
R/W
-
R/W