TEMPERATURE INPUT MODULE REPLACEMENT
The conductor resistance value must meet the condition of 1) + 2)  2k or less.
(In the case of 3-conductor type, the difference between 1) and 2) in the conductor
resistance value must be 10 or less.)
Pt100
Pt100
Q64RD
Q64RD
Conductor
a1
2)
A1
B1
b1
1)
SLD
Q64RD
Conductor
a1
2)
A1
B1
b1
1)
SLD
0.60A
0.17kg
: Compatible,
: Partial change required, ×: Incompatible
Compatibility
Precautions for replacement
The recalculation of internal current
consumption (5VDC) is required.