4
TEMPERATURE INPUT MODULE REPLACEMENT
JIS
Measured temperature
range [°C]
Conversion accuracy at
B
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
R
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
S
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
K
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
E
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
J
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
T
25±0.5°C [°C]
Temperature characteristics
[°C]
Measured temperature
range [°C]
Conversion accuracy at
N
25±0.5°C [°C]
Temperature characteristics
[°C]
Q64TD
Specifications
0 to 600
600 to 800
±3.0
-
±0.4
-50 to 0
0 to 300
±2.5
-
±0.4
-50 to 0
0 to 300
±2.5
-
±0.4
-270 to -200
-200 to 0
Larger value of ±0.5°C, or ±0.5%
of measured temperature
-
Larger value of ±0.06°C, or
±0.2% of measured temperature
-270 to -200
-200 to 0
Larger value of ±0.5°C, or ±0.5%
of measured temperature
-
Larger value of ±0.06°C, or
±0.15% of measured
temperature
-210 to -40
-40 to 750
Larger value of ±0.5°C, or
-
±0.25% of measured
temperature
Larger value of ±0.06°C, or
-
±0.02% of measured
temperature
-270 to -200
-200 to 0
Larger value of ±0.5°C, or ±0.5%
-
of measured temperature
Larger value of ±0.06°C, or
-
±0.1% of measured temperature
-270 to -200
-200 to 0
Larger value of ±0.5°C, or ±0.5%
-
of measured temperature
Larger value of ±0.06°C, or
-
±0.2% of measured temperature
800 to 1700
±2.5
±0.4
300 to 1600
±2.0
±0.3
300 to 1600
±2.0
±0.3
0 to 1200
Larger value of ±0.5°C, or
±0.25% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
0 to 900
Larger value of ±0.5°C, or
±0.25% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
750 to 1200
-
-
0 to 350
Larger value of ±0.5°C, or
±0.25% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
0 to 1250
Larger value of ±0.5°C, or
±0.25% of measured temperature
Larger value of ±0.06°C, or
±0.02% of measured temperature
1700 to
1820
-
1600 to
1760
-
1600 to
1760
-
1200 to
1370
-
900 to 1000
-
-
-
-
350 to 400
-
-
1250 to
1300
-
-
4
- 6

Hide quick links: