Functional Comparison - Mitsubishi Electric MELSEC-A/QnA Series Handbook

Table of Contents

Advertisement

4
TEMPERATURE INPUT MODULE REPLACEMENT

4.2.2 Functional comparison

Item
Temperature conversion function
Conversion enable/disable
function
Disconnection detection function
Temperature conversion value
storage
Input type selection function
Warning output function
Temperature conversion system
Scaling function
Pt100 cold junction compensation
enable/disable setting function
Offset/gain setting function
Error correction function
Online module replacement
4
- 7
Description
Imports temperature data.
Sets whether to enable/disable a
conversion per channel.
Detects a disconnection of the connected
thermocouple of each channel.
Stores imported temperature data in the
buffer memory.
Sets an input type for each channel.
Outputs a warning when the temperature
exceeds the set temperature range.
Processes the detected temperature by
specified method.
Converts a measured temperature value
into a percent value (%) in set width.
Sets whether the cold junction
compensation using the Pt100 attached to
the terminal is performed or not.
Performs linear correction by individually
compensating any given 2 points (offset
value/gain value) within the effective range.
For all input ranges, the function allows
compensating the temperature
measurement value by part of the
compensation value the errors
compensation value.
Replaces a module without stopping the
system.
A616TD
Q64TD
Precautions for replacement
On Q64TD, the channel set
conversion enable automatically
performs the disconnection
detection.
For the Q64TD, this function is
set with the intelligent function
module switch setting.
-
-
-
-
-
Perform the error correction by
-
the offset/gain setting of the
Q64TD.
Replaceable modules during
-
online are the Process CPU and
the Redundant CPU.
: Available, - : Not available

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Melsec q series

Table of Contents