Warning Messages - ABB ACS560 Quick Installation And Start-Up Manual

Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Diagnostics

Warning messages

Code
Warning/Aux
(hex)
code (aux code
visible only on
assistant con-
trol panel and
drive composer)
64FF
Fault reset
A2B1
Overcurrent
A2B3
Earth leakage
Cause
A fault has been reset.
Output current exceeded
internal fault limit.
Load unbalance typically
due to earth fault in motor
or motor cable.
Diagnostics 139
What to do
Event. Informative only.
Check motor load, acceleration
times, earth fault in motor or motor
cables, contactors opening and
closing, start-up data, power factor
correction in capacitors or surge
absorbers in motor cable.
Check for no power factor correc-
tion capacitors or surge absorbers
in motor cable, and no earth fault
in motor or motor cables.
EN
HI

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs560-01

Table of Contents