Code
Fault / Aux.
(hex)
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
1 - Maximum current limit too low
2 - Maximum speed limit or calculated
field weakening point too low
3 - Maximum torque limit too low
4 - Current measurement calibration
not finished within reasonable time
5...8 - Internal error
9 - (Asynchronous motors only). Accel-
eration not finished within reasonable
time.
A - (Asynchronous motors only) .Decel-
eration not finished within reasonable
time.
FF63
STO diagnostics
failure.
FF81
FB A force trip
FF8E
EFB force trip
Cause
SW internal malfunction.
A fault trip command
through fieldbus adapter
A.
A fault trip command
through embedded field-
bus interface.
What to do
B - (Asynchronous motors only) Speed
dropped to zero during ID run.
C - (Permanent magnet motors only).
First acceleration did not finish within
reasonable time.
D - (Permanent magnet motors only).
Second acceleration did not finish
within reasonable time.
E...10 - Internal error
11 - (Synchronous reluctance motors
only). Pulse test error.
12 - Motor too large for advanced
standstill ID run.
13 - (Asynchronous motors only). Motor
data error.
Reboot the control unit (using
parameter 96.08 Control board
boot or by cycling power.
Check the fault information
provided by the PLC.
Check the fault information
provided by the PLC.