Electrical Connection - ABB ACS560 Quick Installation And Start-Up Manual

Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

28 EN - Quick installation and start-up guide
Layout
Electrical installation
Refer to
Electrical installation
wiring accordingly. The BIO-01 module has removable spring clamp terminals. Use
EN
ferrules on the multistranded cables before assembly.
BIO-01 Electrical connection
Sample wiring with the ABB standard macro:
HI
Terminals
External sample connection
Start-up
Install BIO-01
The BIO-01 module is automatically identified by the drive firmware. To configure the
By default, RIIO-01 module is provided in ACS560 standard R0...R2 drives. You can
inputs refer to the ACS480 firmware manual
remove the RIIO-01 module and can install BIO-01 and/or fieldbus adapter module
(+Fxxx).
To install BIO-01 or/and fieldbus module, perform the following steps
Remove the front cover(s). See chapter Electrical installation in the hardware
1.
manual.
1
2
3
on page 55. If you configure the inputs, set up the
Description
Aux. voltage output and prog. digital input
+24V Aux. output +24 V DC, max. 200 mA
DGND Aux. voltage output common
DCOM Digital input common for all
DI1
Stop (0)/Start (1)
DI2
Forward (0)/Reverse (1)
Digital and analog I/O extension BIO-01
DI3
Constant frequency/speed selection
DI4
Constant frequency/speed selection
DI5
Ramp set 1 (0)/Ramp set 2 (1)
DO1
Not configured
AI1
Output frequency/speed ref: 0...10 V
+10V Ref. voltage +10 V DC (max. 10 mA)
GND Analog circuit common / DO common
SCR Signal cable shield / DO screen
Safe torque off (STO)
SGND Safe torque off. Factory connection.
Both circuits must be closed for the
IN1
drive to start.
IN2
OUT1
(3AXD50000047399 [English])
1. Locking tab
2. Fieldbus option module slot
3. Chassis screw
4. I/O connector
BIO-01 I/O extension module 157
4
Base
Internal connection
unit
X
X
X
X
X
X
X
X
X
.