Tighten the nut to a torque of 30 N·m (22 lbf·ft).
•
Tighten the conductor(s) to 40 N·m (30 lbf·ft) for frame R8 or to 70 N·m (52
lbf·ft) for frame R8.
Terminals L1, L2 and L3
•
Remove the combi screw attached to the connector and to its terminal post,
and pull the connector off.
•
Put the conductor under the connector pressure plate and pre-tighten the
conductor.
•
Put the connector back onto the terminal post. Start the combi screw, and
turn it by hand to at least two rotations.
Before using tools, make sure that the nut/screw is not cross-threaded.
Cross-threading can damage the drive and cause danger.
•
Tighten the combi screw to a torque of 30 N·m (22 lbf·ft).
•
Tighten the conductor(s) to 40 N·m (30 lbf·ft) for frame R8 or to 70 N·m (52
lbf·ft) for frame R8.
11. Frames R8 only: If you install parallel cables, install the second grounding shelf
for the parallel power cables (11a). Repeat steps
Frame R8:
12. Install the grounding shelf of the control cables.
13. Reinstall the shroud on the power terminals.
EN - Quick installation and start-up guide 23
M5×25
11b
11a
M5×12
6...11
(11b).
11b
11a
EN