160 Diagnostics
Code
Fault / Aux.
(hex)
code aux code
visible only on
assistant con-
trol panel and
drive com-
poser))
6306
FBA A mapping
file
6481
Task overload
6487
Stack overflow
EN
HI
64A3
Application load-
ing
8006
8007
8008
8009
800A
64A1
Internal file load
64A4
Rating ID fault
64A6
Adaptive pro-
gram
Cause
Fieldbus adapter A map-
ping file read error.
Internal fault.
Note: This fault cannot be
reset.
Internal fault.
Application file incompat-
ible or corrupted.
Not enough memory for
the application.
The application contains
the wrong system library
version.
The application is empty.
The application contains
invalid tasks.
The application contains
an unknown target (sys-
tem) library function.
File read error.
Rating ID load error.
Fault in adaptive program.
What to do
Contact ABB.
Reboot the control unit using para-
meter 96.08 Control board boot or
by cycling power. If the problem
persists, contact ABB.
Reboot the control unit. If the
problem persists, contact ABB.
Check the auxiliary code. See ac-
tions for each code below.
Reduce the size of the application.
Reduce the number of parameter
mappings.
See the drive-specific log generated
by Automation Builder.
Update the system library or rein-
stall
Automation Builder.
See the drive-specific log generated
by Automation Builder.
In Automation Builder, give a
"Clean" command and reload the
application.
In Automation Builder, check applic-
ation task configuration, give a
"Clean all" command, and reload
the application.
Update the system library or rein-
stall Automation Builder.
See the drive-specific log generated
by Automation Builder.
Reboot the control unit. If the
problem persists, contact ABB.
Contact ABB.
Check the fault code extension.