ABB ACS560 Quick Installation And Start-Up Manual page 151

Hide thumbs Also See for ACS560:
Table of Contents

Advertisement

Code
Warning/Aux
(hex)
code (aux code
visible only on
assistant con-
trol panel and
drive composer)
0001
0002
0003
0005
AFAA
Autoreset
AFE1
Emergency stop
(off2)
AFE2
Emergency stop
(off1 or off3)
AFE9
Start delay
AFF5
Override new
start required
AFEB
Run enable miss-
ing
Cause
The drive was started but
was not ready to follow
the autotune command.
Required torque reference
could not be reached be-
fore the drive reached
maximum speed.
Motor could not acceler-
ate/decelerate to maxim-
um/minimum speed.
Motor could not deceler-
ate with full autotune
torque.
A fault is about to be
autoreset.
Emergency stop (mode
selection off2) command.
Emergency stop (mode
selection off1 or off3)
command.
Start delay is active and
the drive will start the
motor after a predefined
delay.
The Safe torque off func-
tion was active and has
been reset while in Over-
ride.
No run enable signal is re-
ceived.
Diagnostics 151
What to do
Make sure the prerequisites of the
autotune run are fulfilled.
See section Before activating the
autotune routine (page 46) in firm-
ware manual.
Decrease torque step (parameter
25.38) or increase speed step
(25.39).
Increase torque step (parameter
25.38) or decrease speed step
(25.39).
Decrease torque step (parameter
25.38) or speed step (25.39).
Informative warning.
Check that it is safe to continue
operation. Then return emergency
stop push button to normal posi-
tion. Restart drive.
Informative warning.
A new start signal is required to
start the drive again.
Check setting of parameter 20.12
Run enable 1 source. Switch on the
signal or check wiring of selected
source.
EN
HI

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Acs560-01

Table of Contents