Verifying The Zero-Sequence Current Reduction From The Winding One Side - Hitachi RET670 Commissioning Manual

Table of Contents

Advertisement

1MRK 504 165-UEN Rev. K
The PSTPDIF function is self-adaptive. Thus, special measures and procedures shall be used during
testing. Off-the-shelf available test sets with associated software and their testing routines for
standard transformer differential protection will not work, in general, for this function. They may work
for special case, when the phase angle shift is zero degree (i.e. as for Yy0 standard power
transformer). However, for specific phase angle shift (e.g. tap position) of the protected PST, which is
different from zero degree, this standard routines cannot be used.
To test this function, it is strongly recommended to use a test set with six current sources and then
follow the sequence-wise testing procedure as explained for the traditional transformer differential
protection in the paper Easy and Intuitive Method for Testing Transformer Differential Relays
published by Hitachi Power grids. This paper is available on the Hitachi Power grids website.
To prepare the function to be tested for specific phase angle shift (e.g. specific tap position) of the
protected PST, proceed as follows:
1.
Make sure that the binary input STOPCOMP into PSTPDIF function has the logical value zero.
2.
Wait for five seconds and inject the rated load using the positive sequence current systems
only on both sides of the PST, which correspond to the set default transformation ratio and
phase angle shift (typically, zero degree). Instructions on magnitude calculation and phase
angles for the six currents to be injected are available in the above mentioned paper. When
currents are injected correctly, check that all three differential currents are approximately 0%
and the bias current is 100%. These values are available as outputs and service values from
the PSTPDIF function.
3.
Slowly (for example, one degree per second) rotate the positive sequence currents (i.e. all
three phases together) for winding two side until the required phase angle shift is achieved.
Note that the rotation in anti-clock-wise direction of winding two positive sequence current will
result in corresponding but negative value of the estimated phase angle shift displayed on the
IED. When PST is of an asymmetrical design, the magnitudes of the currents on the winding
two side shall also be adjusted accordingly. Once the desired tap is reached, make sure that all
three differential currents are still approximately 0% and the bias current is still 100%. Also,
check that DIFRATIO and DIFANGLE outputs have value that corresponds to the PST tap
position at which the function needs to be tested.
4.
Apply the logical value one to the binary input STOPCOMP into PSTPDIF function. The
function will now remember the transformation ratio and phase angle shift, which corresponds
to this particular PST tap. These two values will be stored and used as long as the input
STOPCOMP has a logical value one. To perform this, the IED shall be configured accordingly
beforehand. Typically, one front LHMI key or one binary input can be configured in the
configuration tool to perform this task. If additional security is needed, this action can be only
allowed when the IED is in Testmode.
5.
Interrupt all six currents from the test set and verify that DIFRATIO and DIFANGLE outputs still
have value that corresponds to the PST tap position, at which the function needs to be tested.
The function is now prepared to be tested at this particular tap position in a similar way as the
standard transformer differential protection.
The following sections explain how the PSTPDIF shall be tested for this particular tap position. Note
that, the above procedure and the following tests shall be repeated for every PST tap position, at
which the function needs to be tested.
Note that the following tests can be used for any dedicated tap-position available in the protected
PST. In actual installation, perform these tests for two extrema tap positions, mid-tap position and
one or two more freely selected tap-position(s).
11.3.5.2

Verifying the zero-sequence current reduction from the winding one side

1.
Connect the test set for three-phase currents injection to the current terminals of the IED, which
are connected to the CTs on the winding one side of the power transformer.
2.
Inject current in all three phases with equal magnitudes corresponding to the rated load of the
PST (i.e. 100%) in secondary amperes as given below:
Transformer protection RET670
Commissioning manual
© 2017 - 2022 Hitachi Energy. All rights reserved
Section 11
Testing functionality by secondary injection
GUID-6058B226-4CB6-4721-B7D2-B7678169FB79 v1
97

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents