Hitachi RET670 Commissioning Manual page 149

Table of Contents

Advertisement

1MRK 504 165-UEN Rev. K
frequency of V
I
50
s
EQUATION14059 V1 EN-US
∠I
50s
frequency of I
It
fs
EQUATION14062 V1 EN-US
∠I
tfs
frequency of I
Expected result: the protection function does not issue either start or trip.
The trajectory of the impedance traverses the lens characteristic in zone 2
Preliminary steady state test at 50 Hz
Go to Main menu /Test /Function status /Impedance protection /OutOfStep(78,Ucos) /
OOSPPAM(78,Ucos):1 /Outputs to check the available service values of the function block
OOSPPAM.
Apply the following three-phase symmetrical quantities (the phase angle is related to phase L1):
V
ts
EQUATION14063 V1 EN-US
V
EQUATION14058 V1 EN-US
frequency of V
I
50
s
EQUATION14059 V1 EN-US
∠I
50s
frequency of I
It
fs
EQUATION14062 V1 EN-US
∠I
tfs
frequency of I
Check that the service values (VOLTAGE, CURRENT, R(%), X(%) ) are according to the injected
quantities and that ROTORANG is close to 3.14 rad. For this particular injection the service
values are:
Transformer protection RET670
Commissioning manual
= 50 Hz
ts
I
1
CTs
I
10459
=
×
=
×
50
9000
I
CTp
= 0º
= 50 Hz
50s
I
1
CTs
10459
I
=
×
=
×
tf
I
9000
CTp
= 180º
= 49.5 Hz
tfs
V
VT s
,
0 9
.
V
0 9 11931
.
=
×
×
=
×
t FwdZ
,
V
VT p
,
ForwardX
=
 =
arctan
ts
ForwardR
= 50 Hz
ts
I
1
CTs
I
10459
=
×
=
×
50
9000
I
CTp
= 0º
= 50 Hz
50s
1
I
CTs
I
10459
=
×
=
×
tf
I
9000
CTp
= 0º
= 50 Hz
tf
© 2017 - 2022 Hitachi Energy. All rights reserved
= .
1 162
A
1 162
.
A
=
0 1
.
77 81
.
V
×
=
13 8
.
59 33
.
 =
arctan
82. . 14°
8 19
.
= .
1 162
A
1 162
.
A
=
Section 11
Testing functionality by secondary injection
(Equation 29)
(Equation 30)
GUID-9F0FE404-6D83-4308-9FE4-13259CE7D07A v1
GUID-700F4EA1-B7D9-4B77-829A-433BB67C8A01 v1
(Equation 31)
(Equation 32)
(Equation 33)
(Equation 34)
143

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents