9.5

Verifying the communication

Connect your PC to the substation network and ping the connected IED and the Substation Master
PC, to verify that the communication is working (up to the transport layer). Make sure that the optical
fibers are connected correctly.
After checking the communication, it is time to verify the IEEE C37.118/1344 communication over
both TCP and UDP protocols.
One way to verify the communication up to the application layer is to use a protocol analyzer
connected to the substation bus, and monitor the communication. Alternatively, the PMU Connection
Tester tool can be used to verify the IEEE C37.118/1344 communication. The section
TCP/UDP client communication
to establish an IEEE C37.118 connection with the PMU.
9.5.1

Verifying the IEEE C37.118/1344 TCP communication

After setting both PMU configuration and the TCP client configuration (As explained in sections
Setting the PMU station communication (PMU
(PMU configuration)
Ethernet communication is set up, click Connect on the PMU Connection Tester tool.
IEC140000138 V1 EN-US
Figure 10:
Now it should be possible to see the streaming synchrophasor data. In the Graph tab, observe
the Frequency, data Reporting Rate, Phasor names, and Phase angles of the reported
synchrophasors. Observe the real-time frame details of the Data Frame in the bottom of the
window.
Transformer protection RET670
Commissioning manual
explains how to set the PMU Connection Tester parameters in order
and
Setting the TCP/UDP client
Verifying the TCP communication using PMU Connection Tester
© 2017 - 2022 Hitachi Energy. All rights reserved
Establishing connection and verifying the IEEE C37.118/1344 communication
Report),
Setting the PMU station communication
communication) and making sure that the
IEC140000138-1-en.vsd