Hitachi RET670 Commissioning Manual page 194

Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
StartCurr
IECEQUATION2432 V1 EN-US
Second part of the characteristic (25% of UBase ≤ Restrain voltage ≤ UHighLimit/100*UBase),
valid when setting parameter VDepMode = Slope:
 
IECEQUATION2433 V1 EN-US
Third part of the characteristic (UHighLimit/100*UBase ≤ Restrain voltage):
StartCurr
IECEQUATION2434 V1 EN-US
Example (rated secondary current = 1A):
CT ratio
VT ratio
StartCurr
VDepFact
UHighLimit
IBase
A test for each section of the characteristic of the function VRPVOC may be performed; that
may be achieved by applying the following voltages:
First section of the characteristic:
If VDepMode = Slope, the minimum measured phase-to-phase voltage is lower than
0,25*UBase; if VDepMode = Step, the minimum measured phase-to-phase voltage is lower
than UHighLimit/100*UBase:
Second section of the characteristic only:
If VDepMode = Slope, the minimum measured phase-to-phase voltage is between 0,25*UBase
and UHighLimit/100*UBase:
Last section of the characteristic:
If VDepMode = either Slope or Step, the minimum measured phase-to-phase voltage is higher
than UHighLimit/100*UBase:
4.
Inject the voltages that are related to the first part of the characteristic, and then slowly increase
the phase current IL1 from 0.0 A up to the value the function operates. The START and STOC
signals must be activated when the amplitude of the phase current IL1 is slightly above 0.25 A
188
CT
sec
IBase
×
×
×
100
CTprim
StartCurr
CT
sec
VDepFact
×
×
 ×
IBase
1
100
CTprim
100
(
)
UH
i i ghLimit
25
VT
sec
×
×
UBase
100
VTprim
CT
sec
IBase
×
×
100
CTprim
UL1: Ampl = 10 / √3; Angle = 0°
UL2: Ampl = 10 / √3; Angle = 240°
UL3: Ampl = 100 / √3; Angle = 120°
UL1: Ampl = 50 / √3; Angle = 0°
UL2: Ampl = 50 / √3; Angle = 240°
UL3: Ampl = 100 / √3; Angle = 120°
UL1: Ampl = 105/ √3; Angle = 0°
UL2: Ampl = 105/ √3; Angle = 240°
UL3: Ampl = 105 / √3; Angle = 120°
© 2017 - 2022 Hitachi Energy. All rights reserved
VDepFact
100
25
×
×
Re
strainVoltage
U U Base
100
10 000/1A
10 kV/100 V
100%
25%
100%
10 000 A
10 kV
1MRK 504 165-UEN Rev. K
VT
sec
StartCurr
C C T
sec
×
+
×
×
IBase
VTprim
100
CTprim
 
Transformer protection RET670
Commissioning manual
(Equation 95)
VDepFact
×
100
(Equation 96)
(Equation 97)