Testing functionality by secondary injection
11.4.8.2

Verifying the settings

Measure operating characteristics during constant current conditions. Keep the measured current as
close as possible to its rated value or lower. But make sure it is higher than the set minimum
operating current.
Ensure that the maximum continuous current to the IED does not exceed four times its rated value, if
the measurement of the operating characteristics runs under constant voltage conditions.
The test procedure has to take into consideration that the shaped load encroachment characteristic
is active. It is therefore necessary to check the setting. To verify the settings with the shaped load
encroachment characteristic the test should be carried out according to figures and and tables and .
In cases where the load encroachment characteristic is activated tests according to the adjusted
figures should be carried out.
To verify the settings for the operating points according to the following fault types should be tested:
One phase-to-phase fault
One phase-to-earth fault
The shape of the operating characteristic depends on the values of the setting parameters.
X1set
IEC05000368 V5 EN-US
Figure 37:
122
The figures illustrating the characteristic for the distance protection function can be
used for settings with and without load encroachment. The solid lines designate the
diagram applicable when the load current compensation is active. The solid line and
all test points except 13 are valid for this case.
When the load current compensation is inactive, the dotted lines and test point 13
are valid. Test points 5, 6, and 7 are not valid for this measurement.
X
R1set
2
1
11
10
12
9
8
25% of RFPPZx/2
50% of RFPPZx/2
RFPPZx/2
Distance protection characteristic with test points for phase-to-phase
measurements
© 2017 - 2022 Hitachi Energy. All rights reserved
80%
3
50%
4
5
6
R (Ohm/phase)
7
13
ArgDir
IEC05000368-5-en.vsdx
1MRK 504 165-UEN Rev. K
GUID-1F9FCB40-D43B-48CC-AFD4-2164D04FDCEA v1
Transformer protection RET670
Commissioning manual

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents