Multipurpose Protection; Function Revision History; General Current And Voltage Protection Cvgapc; Built-In Overcurrent Feature (Non-Directional) - Hitachi RET670 Commissioning Manual

Table of Contents

Advertisement

Section 11
Testing functionality by secondary injection
11.9

Multipurpose protection

11.9.1

Function revision history

Document
revision
A
B
C
D
E
F
G
H
J
11.9.2

General current and voltage protection CVGAPC

Prepare the IED for verification of settings as outlined in section
section
One of the facilities within the general current and voltage protection function CVGAPC is that the
value, which is processed and used for evaluation in the function, can be chosen in many different
ways by the setting parameters CurrentInput and VoltageInput.
These setting parameters decide what kind of preprocessing the connected three-phase CT and VT
inputs shall be subjected to. That is, for example, single-phase quantities, phase-to-phase quantities,
positive sequence quantities, negative sequence quantities, maximum quantity from the three-phase
group, minimum quantity from the three-phase group, difference between maximum and minimum
quantities (unbalance) can be derived and then used in the function.
Due to the versatile possibilities of CVGAPC itself, but also the possibilities of logic combinations in
the application configuration of outputs from more than one CVGAPC function block, it is hardly
possible to define a fully covering general commissioning test.
11.9.2.1

Built-in overcurrent feature (non-directional)

Procedure
1.
Go to Main menu /Test /Function test modes /Multipurpose protection /
GeneralCurrentVoltage(GAPC) /CVGAPC:x and make sure that CVGAPC to be tested is
unblocked and other functions that might disturb the evaluation of the test are blocked.
2.
Connect the test set for injection of three-phase currents to the appropriate current terminals of
the IED.
3.
Inject current(s) in a way that relevant measured current (according to setting parameter
CurrentInput) is created from the test set. Increase the current(s) until the low set stage
operates and check against the set operate value.
4.
Decrease the current slowly and check the reset value.
220
Product
History
revision
2.2.1
-
2.2.1
-
2.2.2
-
2.2.3
-
2.2.3
-
2.2.4
-
2.2.4
-
2.2.4
-
2.2.5
The harmonic restraint function changed to freeze the definite and IDMT timers.
The maximum value of the settings IMin1 and IMin2 has been decreased to 1000.0
% of IBase.
Setting BlkLevel2nd was removed from the function.
Previously called stepwise settings t_DefOCx and tResetDef_OCx had their names
changed to t_OCx and tReset_OCx for more clear understanding.
"Preparing for test"
in this chapter.
© 2017 - 2022 Hitachi Energy. All rights reserved
1MRK 504 165-UEN Rev. K
GUID-74F9B9A9-91EB-45BA-A883-6BA325C8B272 v1
"Requirements"
and
Transformer protection RET670
Commissioning manual
SEMOD53552-1 v1
SEMOD56488-3 v4
SEMOD56488-9 v5

Advertisement

Table of Contents
loading

This manual is also suitable for:

Relion 670 series

Table of Contents