Configuring
9.7 Address space
Interface X142 (CPU)
The digital input/outputs of interface X142 are permanently assigned to the CPU.
Table 9- 6
I
Q
STEP 7 assigns the addresses automatically. You can change the addresses in the hardware
configuration of STEP 7, that is, freely assign the start address. The addresses of the channels
are derived from the start address.
You can find the addresses in the device view of the CPU under Device overview and in the
Inspector window, on the General tab under I/O addresses.
You can find a description of the control and feedback interface of the digital input/outputs at
interface X142 in Parameter assignment of digital input/outputs (X142) (Page 160).
Interfaces X122/X132 (SINAMICS Integrated)
The digital inputs and digital inputs/outputs are by default assigned to the drive (CU DO1).
You can use frame interconnection so that these digital inputs and digital inputs/outputs can
also be used by the CPU. To do so, you configure a frame 39x for automatic speed control.
Note
Telegram 393 is set by default during configuration of the SINAMICS Integrated.
Table 9- 7
Scope of input/output data of the digital inputs and digital inputs/outputs X122/X132
Frame
Inputs
390
4 bytes
391
14 bytes
392
30 bytes
393
42 bytes
394
6 bytes
You can find a description of the control and feedback interface of the frames in the
SINAMICS S120/S150 List Manual
(https://support.industry.siemens.com/cs/de/de/view/109822659/en), function diagram 2422
and 2495 to 2500. There, you will also find a description of other selectable telegrams that
are not the focus with the SIMATIC Drive Controller (for example, telegram 395).
See also SINAMICS G/S FAQ: Configuration of standard frames in the TIA Portal
(https://support.industry.siemens.com/cs/ww/en/view/82841762)
STEP 7 assigns the addresses automatically. You can change the addresses in the hardware
configuration of STEP 7, that is, freely assign the start address. The addresses of the channels
are derived from the start address.
156
Scope of the input/output data of the digital input/outputs of interface X142
76 bytes
42 bytes
Outputs
Use of Integrated/CU320-2
4 bytes
No measuring input; DI0 to DI7; DI/DQ8 to DI/DQ15
6 bytes
Two measuring inputs; DI0 to DI7; DI/DQ8 to DI/DQ15
6 bytes
Six measuring inputs; DI0 to DI7; DI/DQ8 to DI/DQ15
8 bytes
8 measuring inputs; DI0 to DI7; DI16, DI17, DI20, DI21, DI/DQ8 to DI/DQ15
(for CU310-2 also: DI18, DI19, DI22, DO16, AI0)
6 bytes
No measuring inputs; DI0 to DI7; DI16, DI17, DI20, DI21, DI/DQ8 to DI/DQ15
(for CU310-2 also: DI18, DI19, DI22, DO16, AI0)
SIMATIC Drive Controller
System Manual, 11/2023, A5E46600094-AD