Maintenance
15.7 Fault reactions with failsafe components
Reintegration of a fail-safe module
The system changes from fail-safe to process values (reintegration of an F-module) either
automatically or only after user acknowledgment in the safety program. If channel errors
occur, it may be necessary to remove and reinsert the F-module. A detailed listing of faults
requiring removal and insertion of the F-module can be found in the section Diagnostic
messages of the respective F-module.
After reintegration, the following occurs:
• In the case of an F-module with inputs, the process data pending at the failsafe inputs is
made available to the safety program again
• In the case of an F-module with outputs, the output values provided in the safety program
are transferred to the failsafe outputs again
Additional information on passivation and reintegration
For additional information on passivation and reintegration of F-I/O, refer to the SIMATIC
Safety, Configuring and Programming
(https://support.industry.siemens.com/cs/ww/en/view/54110126) manual.
Reaction of the F-module with inputs to communication errors
F-modules with inputs respond differently to communication errors compared to other errors.
If a communication error is detected, the current process values remain set at the inputs of
the F-module. The channels are not passivated. The current process values are passivated in
the F-CPU.