Installation of the firmware update
Impermissible plant states possible
Installation of the firmware update causes the CPU to switch to STOP or a distributed
interface module to "station failure". The STOP operating state results in a frame failure at
the drive with a corresponding response at the drive end (for example, OFF3 fast stop,
depends on the parameter assignment). STOP or station failure can have an adverse effect
on the operation of an online process or a machine.
Unexpected operation of a process or a machine can lead to fatal or severe injuries and/or to
material damages.
Before you install the firmware update, make sure that the SIMATIC Drive Controller is not
controlling any active process.
Note
Management of the license conditions and copyright notices of firmware updates
Open-source software is used in the firmware of the SIMATIC Drive Controllers. For legal
reasons, Siemens AG is obliged to publish the original text of the license conditions and
copyright notices. You can find it on the Internet in the FW downloads
(https://support.industry.siemens.com/cs/de/en/view/109773914) and in the scope of supply
of the SIMATIC Drive Controller for the firmware version that has been supplied (see the note
on the type plate at the side).
The license conditions and copyright notices in the scope of delivery can change as a result of
firmware updates. In order to avoid license violations by the reseller and the buyer, if there
are firmware updates, you must pass on the license conditions and copyright notices of the
firmware update to the buyer (for example, by saving them to the SIMATIC Memory Card).
Procedure: online in STEP 7 via Online & diagnostics
Requirement: There is an online connection between the CPU/module and PG/PC.
Proceed as follows to perform an online firmware update via STEP 7:
1. Select the CPU of the SIMATIC Drive Controller in the project tree.
2. Select the "Online & diagnostics" menu command from the shortcut menu.
3. Select the "Firmware update" group in the "Functions" folder.
4. Click the "Browse" button to select the firmware update files in the "Firmware update" area.
5. Select the matching firmware file. The table in the firmware update area lists all modules for
which an update is possible with the selected firmware file.
6. Click the "Run update" button. If the module can interpret the selected file, the file is
downloaded to the module. If you must change the CPU mode, STEP 7 prompts you to do so
with dialogs.