Siemens SINAMICS G150 Operating Instructions Manual page 129

Converter cabinet units 75 kw to 1500 kw
Hide thumbs Also See for SINAMICS G150:
Table of Contents

Advertisement

Restrictions
The following restrictions must be taken into account when a sine-wave filter is used:
● The output frequency is limited to max. 115 Hz (at 500 to 600 V) and 150 Hz (at 380 to
● The modulation type is permanently set to space-vector modulation without
● The maximum output frequency is limited to 85% of the input frequency.
● Maximum permissible motor cable lengths:
● During commissioning, the pulse frequency rises to double the factory setting. This
Table 4- 37
1)
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
480 V).
overmodulation.
– Unshielded cable: max. 450 m
– Shielded cable: max. 300 m
induces current derating, which must be applied to the cabinet unit rated currents listed in
the technical data.
Note
If a filter cannot be parameterized (p0230 ≠ 3), this means that a filter has not been
provided for the cabinet unit. In this case, the cabinet unit must not be operated with a
sine-wave filter.
Technical data for sine-wave filters with SINAMICS G150
Order no.
SINAMICS G150
6SL3710-1GE32-1AAx
6SL3710-1GE32-6AAx
6SL3710-1GE33-1AAx
6SL3710-1GE33-8AAx
6SL3710-1GE35-0AAx
6SL3710-1GF31-8AAx
6SL3710-1GF32-2AAx
The values apply to operation with a sine-wave filter and do not correspond with the rated current
on the type plate.
Voltage
Pulse frequency
[V]
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 380 ... 480
3 AC 500 ... 600
3 AC 500 ... 600
Electrical installation
4.11 Other connections
Output current
[kHz]
[A]
4
172 A
4
216 A
4
273 A
4
331 A
4
382 A
2.5
152 A
2.5
187 A
1).
127

Advertisement