Communication failure when booting or in cyclic operation

If at least one SINAMICS link node does not correctly boot after commissioning or fails in
cyclic operation, then alarm A50005 "Sender was not found on the SINAMICS Link" is output
to the other nodes.
The alarm value contains the number of the sender that cannot be located The alarm is
automatically canceled after the fault has been resolved at the node involved.
If several nodes are involved, the message occurs a multiple number of times consecutively
with different node numbers.
When a node fails in cyclic operation, in addition to alarm A50005, fault F08501 "COMM
BOARD: Setpoint timeout" is output.
6.10.6

Parameter

• r2050[0...31]
• p2051[0...31]
• r2060[0...30]
• p2061[0...30]
• p8811
• p8812[0...1]
• p8835
• p8836
• p8870
• p8871
• p8872
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
CO: IF1 PROFIdrive PZD receive word
CI: IF1 PROFIdrive PZD send word
CO: IF1 PROFIdrive PZD receive double word
CI: IF1 PROFIdrive PZD send double word
SINAMICS Link project selection
SINAMICS Link settings
CBE20 firmware selection
SINAMICS Link address
SINAMICS Link telegram word PZD receive
SINAMICS Link telegram word PZD send
SINAMICS Link address PZD receive