12.2 General data
Current derating as a function of the pulse frequency
When the pulse frequency is increased, the derating factor of the output current must be
taken into account. This derating factor must be applied to the currents specified in the
technical specifications for the cabinet units.
Table 12- 6
Derating factor of the output current as a function of the pulse frequency for devices with a rated pulse
frequency of 2 kHz
Order no.
6SL3710-...
1GE32-1_Ax
1GE32-6_Ax
1GE33-1_Ax
1GE33-8_Ax
1GE35-0_Ax
Table 12- 7
Derating factor of the output current as a function of the pulse frequency for units with a rated pulse frequency
of 1.25 kHz
Order no.
6SL3710-...
1GE36-1_Ax
1GE37-5_Ax
1GE38-4_Ax
1GE41-0_Ax
2GE41-1AAx
2GE41-4AAx
2GE41-6AAx
1GF31-8_Ax
1GF32-2_Ax
1GF32-6_Ax
1GF33-3_Ax
1GF34-1_Ax
1GF34-7_Ax
1GF35-8_Ax
1GF37-4_Ax
1GF38-1_Ax
2GF38-6AAx
2GF41-1AAx
2GF41-4AAx
584
Power
Output current
[kW]
at 2 kHz [A]
Supply voltage 380 V ... 480 V 3 AC
110
132
160
200
250
Power
Output current
[kW]
at 1.25 kHz [A]
Supply voltage 380 V ... 480 V 3 AC
315
400
450
560
630
710
900
Supply voltage 500 V ... 600 V 3 AC
110
132
160
200
250
315
400
500
560
630
710
1000
210
260
310
380
490
Derating factor
605
745
840
985
1120
1380
1560
175
215
260
330
410
465
575
735
810
860
1070
1360
Operating Instructions, 03/2012, A5E03263466A
Derating factor at 4 kHz
82 %
83 %
88 %
87 %
78 %
Derating factor
at 2.5 kHz
at 5 kHz
72 %
72 %
79 %
87 %
72 %
72 %
79 %
87 %
87 %
88 %
82 %
82 %
87 %
85 %
79 %
72 %
87 %
85 %
79 %
Converter cabinet units
60 %
60 %
60 %
60 %
60 %
60 %
60 %
60 %
60 %
60 %
55 %
55 %
55 %
55 %
55 %
55 %
55 %
55 %
55 %