Note
The integrated safety functions, starting from the Safety Integrated (SI) input terminals of the
SINAMICS components (Control Unit, Motor Module), satisfy the requirements according to
EN 61800-5-2, EN 60204-1, EN ISO 13849-1 Category 3 (formerly EN 954-1) for
Performance Level (PL) d and EN 61508 SIL 2.
In combination with option K82, the requirements specified in EN 61800-5-2, EN 60204-1 as
well as in EN ISO 13849-1 Category 3 (formerly EN 954-1) are satisfied for Performance
Level (PL) d and EN 61508 SIL 2.
Note
Detailed and comprehensive instructions and information for the Safety Integrated functions
can be found in the accompanying Function Manual. This manual is available as additional
documentation on the customer DVD supplied with the device.
4.11.28

Safe Brake Adapter SBA 230 V AC (option K88)

Description
Safe Brake Control (SBC) is a safety function that is used in safety-related applications. In
the no-current state, the brake acts on the motor of the drive using spring force. The brake is
released (opened) when current flows through it (=low active).
The Safe Brake Adapter 230 V AC is installed in the cabinet unit in the factory. An infeed is
connected to terminal -X12 on the Safe Brake Adapter for the power supply. For control, a
connection is established between the Safe Brake Adapter and the Control Interface Module
using a cable harness installed in the factory.
For controlling the brake, on the plant side, a connection must be established between
terminal -X14 on the Safe Brake Adapter and the brake.
If, on the plant site, a 24 V DC brake is connected to option K88, Safe Brake Adapter 230 V
AC, then this can damage the Safe Brake Adapter. This can result in the following
undesirable effects:
• Closing the brake is not displayed on the LEDS.
• The fuse is ruptured.
• The contact service life of the relay is reduced.
Converter cabinet units
Operating Instructions, 03/2012, A5E03263466A
WARNING
Electrical installation
4.11 Other connections
181