Configuring

6.5 Configuring the Speed-Control Axis technology object

6.5
Configuring the Speed-Control Axis technology object
6.5.1

Configuration - Basic Parameters

Configure the basic properties of the technology object in the "Basic Parameters"
configuration window.
Axis name
Define the name of the speed axis in this field. The technology object is listed in the project
navigation under this name. The tags of the speed axis can be used in the user program
under this name.
Speed unit
Select the measuring system for speed from the drop-down list box.
6.5.2

Hardware interface

6.5.2.1

Configuration - Drive

In the "Drive" configuration window, configure which drive type and which drive you want to
use.
Drive type
In the drop-down list, select whether you want to deploy a PROFIdrive drive or a drive with
an analog drive connection.
PROFIdrive drives are connected to the controller by means of a digital communication
system (PROFINET or PROFIBUS). The communication occurs via PROFIdrive frames.
Drives with an analog drive connection receive the setpoint speed via an analog output
signal (e.g. from -10 V to +10 V) from the PLC.
Drive (drive type: PROFIdrive)
In the "Drive" field, select an already configured PROFIdrive drive / slot. If a PROFIdrive
drive was selected, then it can be configured using the "Device configuration" button.
Switch to the device configuration, and add a PROFIdrive drive in the network view, in the
event that no PROFIdrive drive can be selected.