Disturbance Recorder (“Disturb Recorder” Menu) - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Setting
MiCOM P40 Agile P442, P444
Menu Text
RECORD CONTROL
System Event
Disabling this setting means that no System Events will be generated.
Fault Rec. Event
Disabling this setting means that no event will be generated for any fault that produces a
fault record.
Maint. Rec. Event
Disabling this setting means that no event will be generated for any occurrence that
produces a maintenance record.
Protection Event
Disabling this setting means that any operation of protection elements will not be logged
as an event.
Clear Dist Recs
Selecting "Yes" will cause the existing disturbance records to be cleared and an event will
be generated indicating that the disturbance records have been erased.
DDB 31 - 0
Displays the status of DDB signals 0 – 31.
DDB 2047 - 2016
Displays the status of DDB signals2016– 2047.
3.5
Disturbance recorder ("Disturb recorder" menu)
The integral disturbance recorder has an area of memory specifically set aside for record
storage. The number of records that may be stored is dependent on the selected recording
duration but the relays typically have the capability of storing a minimum of 20 records, each
of 10.5 second duration.
NOTE:
Disturbance records continue to be recorded until the available memory is exhausted, at
which time the oldest record(s) are overwritten to make space for the newest one.
The recorder stores actual samples which are taken at a rate of 48 samples per cycle.
Each disturbance record consists of eight analogue data channels and 64 digital data
channels. Note that the relevant CT and VT ratios for the analogue channels are also
extracted to enable scaling to primary quantities).
Menu Text
DISTURB RECORDER
Duration
This sets the overall recording time.
Trigger Position
Default Setting
Enabled
Enabled
Enabled
Enabled
No
11111111111111111111111111111111
11111111111111111111111111111111
1. Compressed Disturbance Recorder used for Kbus/Modbus/DNP3
reach that typical size value (10.5 sec duration)
2. Uncompressed Disturbance Recorder used for IEC 60870-5/103
could be limited to 2 or 3 seconds.
Default Setting
600 s
33.3%
Setting Range
Min.
Max.
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
Enabled or Disabled
No or Yes
Setting Range
Min.
Max.
100.0 ms
10.5 s
0.0%
100.0%
P44x/EN ST/Hb6
(ST) 4-45
Step Size
Step Size
10.00 ms
0.10 %