GE MiCOM P40 Agile Technical Manual page 371

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

Programmable Logic
MiCOM 40 Agile P442, P444
Ordinal
English Text
262
T2
1095
T2 Timer Block
263
T3
1098
T3 Timer Block
264
T4
1099
T4 Timer Block
333
tBF1 Trip
334
tBF2 Trip
206
Test Mode Acq
369
Thermal Alarm
1092
Time Synch
830 to
Timer in 1 to
845
Timer in 16
830 to
Timer in 1 to
861
Timer in 16
862 to
Timer in 1 to
893
Timer in 16
846 to
Timer out 1 to
861
Timer out 16
314
TOC Start A
315
TOC Start B
316
TOC Start C
313
TOR Enable
1032
TPAR Enable
368
Trace Trig OK
1024
Trip LED
370
Trip Thermal
265
Tzp
1096
TZp Timer Block
Description
Distance time-delay in zone 2 tZ2 elapsed (1 = end of
timer)
Timer block T2 input
Distance time-delay in zone 3 tZ3elapsed (1 = end of
timer)
Timer block T3 input
Distance time-delay in zone 4 tZ4 elapsed (1 = end of
timer)
Timer block T4 input
Circuit Breaker failure on any trip, delayed by "CB Fail
1 Timer" (setting in "CB Fail" logic)
Circuit Breaker failure on any trip, delayed by "CB Fail
2 Timer" (setting in "CB Fail" logic)
Relays with IEC 61850 9-2 Ethernet board only with
software version up to D4.x - Any Logical Node is in
"Test Mode"
Alarm from Thermal Overload function picks up
External time synchronisation input
Hardware version K - PSL Input to Auxiliary Timer 1
to PSL Input to Auxiliary Timer 16
Hardware version J - PSL Input to Auxiliary Timer 1
to PSL Input to Auxiliary Timer 32
Hardware version J - PSL Output from Auxiliary Timer
1
to PSL Output from Auxiliary Timer 32
Hardware version K - PSL Ouput from Auxiliary Timer
1
PSL Ouput from Auxiliary Timer 16
Trip on Close start on phase A: indicates a trip order
on phase A has been issued by the SOTF level
detectors (Pickup time-delay = 20 ms)
Trip on Close start on phase B: indicates a trip order
on phase B has been issued by the SOTF level
detectors (Pickup time-delay = 20 ms)
Trip on Close start on phase C: indicates a trip order
on phase C has been issued by the SOTF level
detectors (Pickup time-delay = 20 ms)
Trip On Reclose enable: indicates the TOR logic is
activated in the relay
Set to 1= 500 ms pulse initiated by:
'I A/R Reclaim' (internal) OR 'A/R reclaim' (External
Input)
OR Any pole open for more than 200 ms
Reset 500 ms after Any pole dead stops
Enable internal three pole autorecloser
Set with Opto input (if linked by PSL) is energized (>
1s).
At 1: 3P AR internal is enabled in the AR logic
At 0: AR 3P internal is disabled (even if set in MiCOM
S1 Agile). 1P cycle available if SPAR =1
Triggering trace has operated correctly
LED trip
Trip with Thermal Overload fucntion (timer issued)
Distance time-delay in zone p tZp elapsed (1 = end of
timer)
Timer block TZp input
P44x/EN PL/Hb6
(PL) 6-51
Source
PSL (OUT)
Distance
PSL
PSL (OUT)
Distance
PSL
PSL (OUT)
Distance
PSL
PSL (OUT)
Breaker
failure
PSL (OUT)
Breaker
failure
PSL (OUT)
PSL (OUT)
PSL(IN)
Auxiliary
Timer
Auxiliary
Timer
Auxiliary
Timer
Auxiliary
Timer
PSL (OUT)
SOTF
PSL (OUT)
SOTF
PSL (OUT)
SOTF
PSL (OUT)
TOR
PSL (IN)
Autorecloser
PSL (OUT)
PSL (OUT)
PSL (OUT)
Distance
PSL

Advertisement

Table of Contents
loading

This manual is also suitable for:

P442P444

Table of Contents