Ordinal
English Text
455
LBlinder DetectBN
456
LBlinder DetectCN
457
LBlinder DetectAB
458
LBlinder DetectBC
459
LBlinder DetectCA
460
LB PowerSwing
1.2

Factory default programmable scheme logic

1.2.1
Logic input mapping
The default mappings for each of the opto-isolated inputs are as shown in the following table
(PSL are equivalent for P442 and P444):
Opto
Input
P442 Relay
Channel Receive
1
(Distance or DEF)
Channel out of Service
2
(Distance or DEF)
MCB/VTS Main
3
(Z measurement-Dist)
Block Autoreclose (BAR)
4
(Lockout)
5
Circuit Breaker Healthy
Circuit breaker Manual
6
Close external order
7
Reset Lockout
Disable Autoreclose
8
(1-pole and 3-pole)
9
Not allocated
10
Not allocated
11
Not allocated
12
Not allocated
13
Not allocated
14
Not allocated
15
Not allocated
16
Not allocated
17
18
19
20
Description
Load Blinder Detection in Loop BN: Cell at 1 indicates
the Impedance is located within the BN loop Load
Blinder Region.
Load Blinder Detection in Loop CN: Cell at 1 indicates
the Impedance is located within the CN loop Load
Blinder Region.
Load Blinder Detection in Loop AB: Cell at 1 indicates
the Impedance is located within the AB loop Load
Blinder Region.
Load Blinder Detection in Loop BC: Cell at 1 indicates
the Impedance is located within the BC loop Load
Blinder Region.
Load Blinder Detection in Loop CA: Cell at 1 indicates
the Impedance is located within the CA loop Load
Blinder Region.
Power Swing Detected within Load Blinder Region
P444 Relay
Channel Receive
(Distance or DEF)
Channel out of Service
(Distance or DEF)
MCB/VTS Main
(Z measurement-Dist)
Block Autoreclose (BAR)
(Lockout)
Circuit Breaker Healthy
Circuit breaker Manual
Close external order
Reset Lockout
Disable Autoreclose
(1-pole and 3-pole)
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Programmable Logic
MiCOM 40 Agile P442, P444
Source
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance
PSL (OUT)
Distance

Advertisement

Table of Contents
loading

This manual is also suitable for:

P442P444

Table of Contents