Algorithm For Pole Dead Detection; Description Of The Open Pole Detection Algorithm - GE MiCOM P40 Agile Technical Manual

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN AP/Hb6
(AP) 5-120
I
+
I<
I
+
I<
Figure 90: Algorithm for pole dead detection

Description of the open pole detection algorithm:

Each half cycle after the current crosses zero, the algorithm detects whether the current is
higher than the I< threshold. If it is, then the detection timer is restarted, if it is lower than the
set value then nothing is done.
At the end of the detection timer, open pole decision is given by the algorithm.
Time delay value given by: (Number of Samples/2 + 2) * ((1/Freq)/Number of Samples)
Where:
T
=
or
T
=
The current used is the unfiltered current (only the analog low pass filter is used)
Example:
In the first example, the line current is broken by the opening of the circuit breaker.
The detection is confirmed 3ms after the pole is opened.
In the second example, some residual current remains due to the CT. The detection is
confirmed 12 / 15 ms after the pole is opened.
+
-
+
-
13,3 ms (50 Hz)
11,1 ms (60 Hz)
MiCOM P40 Agile P442, P444
Pole Live
+
T
T
-
-
+
-
-
Application Notes
Pole Dead
T
P0553ENa