Programmable Logic
MiCOM 40 Agile P442, P444
Opto
Input
P442 Relay
21
22
23
24
1.2.2
Relay output contact mapping
The default mappings and conditioning for each of the relay output contacts are shown in the
following table (PSL are equivalent for P442/444):
Relay
Contact
P442 Relay
1
TripA+B+C & Z1 [straight]
2
Any Trip Phase A [straight]
3
Any Trip Phase B [straight]
4
Any Trip Phase C [straight]
Signal send (Dist. or DEF)
5
[straight]
6
Any Protection Start [straight] Any Protection Start [straight]
7
Any Trip [straight]
8
General Alarm [straight]
DEF A+B+C Trip + IN>2Trip
9
+ IN>3Trip
[straight]
Dist. Trip & Any Zone & Dist
10
Unb CR [straight]
Autoreclose lockout
11
[straight]
Autoreclose 1P + 3P
12
cycle in progress [straight]
13
A/R Close [straight]
Power Swing Detected
14
[straight]
15
Not allocated
16
Not allocated
17
Not allocated
18
Not allocated
19
Not allocated
20
Not allocated
21
Not allocated
22
Not allocated
23
24
25
26
27
28
29
30
31
P444 Relay
Not allocated
Not allocated
Not allocated
Not allocated
P444 Relay
TripA+B+C & Z1 [straight]
Any Trip Phase A [straight]
Any Trip Phase B [straight]
Any Trip Phase C [straight]
Signal send (Dist. or DEF)
[straight]
Any Trip [straight]
General Alarm [straight]
DEF A+B+C Trip + IN>2Trip
+ IN>3Trip
[straight]
Dist. Trip & Any Zone & Dist
Unb CR [straight]
Autoreclose lockout
[straight]
Autoreclose 1P + 3P
cycle in progress [straight]
A/R Close [straight]
Power Swing Detected
[straight]
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated
Not allocated