P44x/EN ST/Hb6
(ST) 4-14
Menu text
GROUP 1 – DISTANCE ELEMENTS
Z1X
R1G
R1G: Resistive reach (Earth fault element, refer to P44x/EN AP for resistive reach
calculation (earth and phase) setting).
R1Ph
R1Ph: Resistive reach (phase fault element, refer to P44x/EN AP for resistive reach
calculation (earth and phase) settings).
tZ1
Zone 1 time delay (TZ1): Zone 1 time delay setting (refer to P44x/EN AP for setting).
KZ2 Res Comp
KZ2 Angle
Zone 2 compensation (KZ2 residual compensation and kZ2 angle) setting.
Z2
R2G
R2G: resistive reach – Earth fault element setting for zone 2.
R2Ph
R2Ph: Resistive reach – phase fault elements setting for zone 2.
tZ2
Zone 2 time delay (TZ2) setting.
KZ3/4 Res Comp
KZ3/4 Angle
Zone 3 and 4 compensations (KZ3/4 residual compensation and kZ3/4 angle) setting.
Z3
R3G - R4G
R3G – R4G: Resistive reach – Earth fault elements setting for zones 3 and 4.
R3Ph - R4Ph
R3Ph – R4Ph: resistive reach – Phase fault elements setting for zones 3 and 4.
tZ3
Zone 3 time delay (TZ3) setting.
Z4
tZ4
Zone 4 time delay (TZ4) setting.
Zone P - Direct.
KZp Res Comp
KZp Angle
Zone P compensation (KZp residual compensation and kZp angle).
Zp
Default setting
15/In Ω
0.001/In Ω
10/In Ω
0
10/In Ω
0
0
0
1
0
20/In Ω
0.001/In Ω
20/In Ω
0
20/In Ω
0
0.2s
0
1
0
30/In Ω
0.001/In Ω
30/In Ω
0
30/In Ω
0
0.6s
0
40/In Ω
0.001/In Ω
1s
0
Directional Fwd
Directional Fwd or Directional Rev
1
0
25/In Ω
0.001/In Ω
MiCOM P40 Agile P442, P444
Setting range
Min
Max
500/In Ω
400/In Ω
400/In Ω
10s
7
360°
500/In Ω
400/In Ω
400/In Ω
10s
7
360°
500/In Ω
400/In Ω
400/In Ω
10s
500/In Ω
10s
7
360°
500/In Ω
Setting
Step size
0.001/In Ω
0.01/In Ω
0.01/In Ω
0.002s
0.001
0.1°
0.001/In Ω
0.01/In Ω
0.01/In Ω
0.01s
0.01
0.1°
0.001/In Ω
0.01/In Ω
0.01/In Ω
0.01s
0.01/In Ω
0.01s
0.001
0.1°
0.001/In Ω