P44x/EN SC/Hb6
(SC) 12-38
counters having different point numbers to their running counterparts. For example, object
20 point 3 (running counter) might have its frozen value reported as object 21 point 1.
5.7.3
Object 30
For the analog inputs, object 30, the same selection options for classes 0, 1, 2 and 3 are
available as for object 1. In addition to these options, which behave in exactly the same way
as for object 1, it is possible to change the deadband setting for each point. The minimum
and maximum values and the resolution of the deadband settings are defined in the device
profile document; MiCOM S1 Agile will allow the deadband to be set to any value within
these constraints.
SCADA Communications
MiCOM P40 Agile P442, P444