GE MiCOM P40 Agile Technical Manual page 44

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN TD/Hb6
(TD) 2-18
CIRCUIT BREAKER FAIL AND I<
PROTECTION (CB FAIL & I<)
Circuit Breaker Fail
CB Fail 1 Status:
CB Fail 1 timer:
0 to 10 s (step 0.01 s)
CB Fail 2 Status:
CB Fail 2 timer:
0 to 10 s (step 0.01 s)
CB Fail Non I reset:
∗ I< only,
∗ CB Open & I<,
∗ Prot reset & I<,
∗ Prot reset or I<,
∗ Disable
CBF Ext reset:
∗ I< only,
∗ CB Open & I<,
∗ Prot reset & I<,
∗ Prot reset or I<,
∗ Disable
Undercurrent I<:
I< current set:
0.05×In to 3.2×In (step 0.01×In)
NON-PROTECTION FUNCTIONS
SETTINGS
CB CONDITION
CB Operations (number): 0 to 10000 (step 1)
CBA Operations:
CBB Operations:
CBC Operations:
Total IA Broken:
0 to 25000 In^ (step 1 In^)
Total IB Broken:
0 to 25000 In^ (step 1 In^)
Total IC Broken:
0 to 25000 In^ (step 1 In^)
CB Operate time:
0 to 0.5 s (step 0.001)
Reset CB Data:
Total 1P Reclosures:
Total 3P Reclosures:
Reset Total A/R:
CB MONITOR SETUP
Broken I^:
I^Maintenance:
Alarm Enabled/Alarm Disabled
1In^ to 25000In^ (step 1In^)
I^ Lockout:
Alarm Enabled/Alarm Disabled
1In^ to 25000In^ (step 1In^)
Number CB Operations Maintenance:
Alarm Enabled/Alarm Disabled
CB Operating time Maintenance:
Alarm Enabled/Alarm Disabled
0.005 s to 0.5 s (step 0.001 s)
CB Operating time Lockout Maintenance:
Alarm Enabled/Alarm Disabled
0.005 s to 0.5 s (step 0.001 s)
CB Fault frequency:
∗ Lock:
Alarm Enabled/Alarm Disabled
∗ Count:
Fault frequency time:
Lockout reset:
Reset Lockout by:
CB Close/User interface
Man Close reset delay: 0.01 to 600 (step 1)
Disabled/Enabled
Disabled/Enabled
0 to 10000 (step 1)
0 to 10000 (step 1)
0 to 10000 (step 1)
Yes/No
0 to 0.85 s (0.001)
0 to 0.85 s (0.001)
Yes/No
0 to 2 (step 0.1)
1 to 10000 (step 1)
0 to 9999 (step 1)
0 to 9999 s (step 1 s)
Yes/No
MiCOM P40 Agile P442, P444
CB CONTROL
CB Control by:
∗ Disabled,
∗ Local,
∗ Remote,
∗ Local + Remote,
∗ Opto-input,
∗ Opto input + Local,
∗ Opto input + Remote,
∗ Opto input + Local + Remote.
Close Pulse Time: 0.1 s to 10 s (step 0.01 s)
Trip Pulse Time:
0.1 s to 5 s (step 0.01 s)
Man Close Delay:0.01 s to 600 s (step 0.01 s)
Healthy Window:0.01 s to 9999 s (step 0.01 s)
Check Synchronizing (C/S) Window:
0.01 s to 9999 s (step 0.01 s)
A/R Single Pole:
A/R Three Pole:
CT AND VT RATIOS
Main VT ratios:
100 V to 1M V (step 1 V)
Main VT's Secondary:
80 V to 140 V (step 1 V)
4th VT:
∗ Primary:
100 V to 1M V (step 1 V)
∗ Secondary
80 V to 140 V (step 1 V)
Phase CT:
∗ Primary:
∗ Secondary
Mutual Compensation CT: (can also be used
for Residual Current measurement)
∗ Primary:
∗ Secondary
Check Synchronizing (C/S) input:
A (phase A)–N (Neutral)/
B–B/C–N/A–B/B–C/C–A
Main VT Location:
CT polarity:
Measured VN
Measured IN
SEQUENCE OF EVENT RECORDER
(RECORD CONTROL)
Clear Events:
Clear Faults:
Clear Maint:
Alarm Event:
Relay O/P Event:
Opto Input Event:
System Event:
Fault Rec Event:
Maint Rec Event:
Protection Event:
DDB 31 – 0: (up to):
DDB 2047 – 2016:
Binary function link strings, selecting which
DDB signals will be stored as events, and
which will be filtered out
Technical Data
Enabled/Disabled
Enabled/Disabled
1A to 30 kA (step 1A)
1A/5A
1A to 30 kA (step 1A)
1A/5A
Line/Bus
Standard/Inverted
Disabled
Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled
Enabled/Disabled