GE MiCOM P40 Agile Technical Manual page 392

Hide thumbs Also See for MiCOM P40 Agile:
Table of Contents

Advertisement

P44x/EN MR/Hb6
(MR) 7-6
VIEW RECORDS
LCD Reference
Earth Fault
Earth Fault
Aided DEF
Aided DEF
Undercurrent
Undercurrent
Undervoltage
Undervoltage
Overvoltage
Overvoltage
Overfrequency
Overfrequency
Underfrequency
Underfrequency
Res. Overvoltage
Res. Overvoltage
Breaker Fail
Supervision
LOL
SOTF/TOR
TOC
TOC
Weak infeed
ZSP
ZSP
User
Faulted Phase
Start Elements
Trip Elements1
Validities
Time & Date
Fault Alarms
System Frequency
Fault duration
Relay Trip Time
Description
Start IN>1, Start IN>2, Start IN>3 or Start IN>4
Trip IN>1, Trip IN>2, Trip IN>3 or Trip IN>4
DEF> Start
DEF> Trip
Start I<1, Start I<2
Trip I<1, Trip I<2
Start V<1, Start V<2, Start V<3 or Start V<4
Trip V<1, Trip V<2, Trip V<3 or Trip V<4
Start V>1, Start V>2, Start V>3 or Start V>4
Trip V>1, Trip V>2, Trip V>3 or Trip V>4
Start F>1 or Start F>2
Trip F>1 or Trip F>2
Start F<1, Start F<2, Start F<3 or Start F<4
Trip F<1, Trip F<2, Trip F<3 or Trip F<4
Start VN>1 or Start VN>2
Trip VN>1 or Trip VN>2
CB Fail 1 or CB Fail 2
CTS, VTS or CVTS
Trip
Trip
Start
Trip
Trip
Start
Trip
Trip
Phase initiating fault recorder starts: Start A, Start B, Start C, Start N, Trip
A, Trip B, Trip C, Trip N
General Start, Start I>1, Start I>2, Start I>3, Start I>4, Start I2>1, Start
IN>1, Start IN>2, Start IN>3, Start IN>4, Start DEF, Start V<1, Start V<2,
Start V>1, Start V>2, Start Broken Cond, Start LOL, Start Distance, Start
TOC, Start Zero Seq. Pow., Start PAP, Thermal Alarm, Start I2>2, Start
I2>3, Start I2>4, Start VN>1 or Start VN>2
Any Trip, Trip I>1, Trip I>2, Trip I>3, Trip I>4, Trip I2>1, Trip IN>1, Trip
IN>2, Trip IN>3, Trip IN>4, Trip DEF, Trip V<1, Trip V<2, Trip V>1, Trip
V>2, Trip Broken line, Trip Z1, Trip Z2, Trip Z3, Trip Zp, Trip Z4, Trip Z2
Aided, Trip LOL, Trip Soft Tor, Trip WI, Trip CB Fail1, Trip CB Fail2, Trip
Zero Seq. Pow., Trip PAP, Trip Thermal or Trip User
"Measurements and Location are not valid" or "Measurements is valid" or
"Location is valid"
Time & Date Stamp for the event given by the internal Real Time Clock.
VT Fail Alarm, CT Fail Alarm, CB Status Alarm, AR Lockout Shot >, V<1
Alarm, V<2 Alarm, V>1 Alarm, V>2 Alarm, COS Alarm, CVT Fail Alarm,
V<3 Alarm, V<4 Alarm, V>3 Alarm or V>4 Alarm
50.00 Hz, 60.00 Hz
Duration of the fault
Time and date of fault relay tripping
Measurements and Recording