See related parameter "Frequency arriving at detection width" [E1.04].
● 5: Frequency level detection signal (FDT1)
● 6: Frequency level detection signal (FDT2)
See related parameters [E1.05] ~ [E1.08].
● 7: Simple PLC phase completion indication
When PLC mode [E2.30] = 1, 2 or 3, this terminal outputs a pulse at the end of every
PLC stage. When a stage is finished a pulse is output with the duration of 0.5s. If
one of the stages has a running time of 0.0s, this stage will be directly jumped over
and there will be no pulse output. For details of simple PLC control, see parameters
[E2.10]~[E2.16] and [E2.30]~[E2.50].
Fig.8-34: Simple PLC phase completion indication
If the running time of one of the stages is so short that it is finished before
the "phase completion" signal of the previous stage is deactivated, the sig‐
nal remains active and the pulse duration calculation is restarted.
● 8: Simple PLC cycle completion indication
When PLC mode [E2.30]=1, 2 or 3, this terminal outputs a pulse (duration 0.5s) at
the end of every cycle. See parameters [E2.10] ~ [E2.16] and [E2.30] ~ [E2.50].
Fig.8-35:
[E2.30]=1, 2 or 3