Bosch Rexroth AG
Diagnosis
Error
Error name Possible reason
code
PSr-
EEPr
ESS-
CE5-
136/235
10 V overload situations on
I/O board
EMC problems at customer
I/O interface
Internal problem
Power failure while write /
read
If error happens at normal
power on, problems with ope‐
rating panel
Parameter compatibility be‐
cause firmware update
Soft start resistor value has
been changed due to high
over temperature
Mains input is unstable
Mains input is weak
An input phase loss during
start up (3 phase)
Main circuit capacitor deterio‐
ration
Problem with CPU on main
board
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Solution
Remove the overload situation
Remove the environmental inter‐
ference or EMI
● Check the wiring of control cir‐
cuit, main circuit and ground to
find out the source of interfer‐
ence
● Replace the frequency con‐
verter
Parameter initialization
Replace the operating panel
Should be solved during develop‐
ment
Replace the frequency converter
Check the input power supply
Increase the power capacity
Remove the input phase loss sit‐
uation
Replace the frequency converter
● Check the wiring
● If it fails again, contact with
technical service