Rexroth Frequency Converter EFC 3600
N.O.:
– If terminal is inactive (open), there is no error.
– If terminal is active (closed), there is an error.
● 21: External RESET input
This function works in the same manner as the keyboard error reset function does,
which allows remote fault reset. "External RESET input" depends on the edge of the
input signal (signal changes from inactive to active).
● 22: The second run command source enabled
This function is used to switch RUN / STOP command source between the first
channel ([b1.02]) and the second channel ([b1.17]). When this terminal is inactive,
the first channel ([b1.02]) is active; when this terminal is active, the second channel
([b1.17]) is active.
● 23: Forward (FWD)
● 24: Reverse (REV)
These two functions are used for RUN / STOP command control, see parameter
[E0.00].
● 25: Forward jogging
● 26: Reverse jogging
For jogging functions, see parameters [S3.00]~[S3.02].
● 27: Counting input
● 28: Counting clear
The above two functions are counting functions of an external signal. See parame‐
ters [E1.13] and [E1.14].
E0.10
Analog input voltage (AIV) channel gain k1
Setting range
0.00 ~ 10.00
Minimum unit
0.01
Factory default
1.00
E0.12
Analog input current (AIC) channel gain k3
Setting range
0.00 ~ 10.00
Minimum unit
0.01
Factory default
1.00
E0.15
Analog channel filtering time
Setting range
0.000 ~ 2.000s
Minimum unit
0.001s
Factory default
0.100s
E0.20
Analog setting curve selection
Bosch Rexroth AG
Parameter Settings
97/235