Commissioning

7.1
Checking and Preparation before Commissioning
WARNING
Ensure the plastic enclosure is in place before the device is powered on. Wait for at
least 10 minutes after powering off to allow the DC capacitor being discharged, and do
not remove the upper cover during this period.
① Check if the wiring is correct. Particularly, ensure that the output terminals U, V and
W of the frequency converter are not connected to the power supply and that the
ground terminal is well connected.
② Ensure that there are no short circuits between terminals, live terminals or short cir‐
cuit to ground.
③ Ensure that terminal connections, connectors and screws are secure.
④ Ensure that the motor is not connected to any load.
⑤ Check that all switches are off before powering on, to ensure that the frequency con‐
verter will not be started and no unexpected action occurs.
⑥ It is suggested to connect U, V, W of the frequency converter to corresponding U, V,
W of the motor.
Bosch Rexroth AG
Commissioning
47/235