Rexroth Frequency Converter EFC 3600
Fig.8-4: Priority of frequency source
● When the combination of two resources is inactive:
The two frequency resources can be switched via external terminal ([E0.01] ~
[E0.05]=18), for more details, please see "Multi-function digital input terminals".
– When the combination is disabled and switching terminal is inactive, frequency
command value is given by the first frequency setting source.
– When the combination is disabled and switching terminal is active, frequency
command value is given by the second frequency setting source.
b1.16
Second frequency setting source
Setting range
0 ~ 6
Minimum unit
1
Factory default
2
● 0: Given by panel potentiometer
● 1: Given by panel digital setting
● 2: Given by external analog AIV
● 3: Given by external analog AIC
● 4: Set by external UP / DOWN terminals
● 5: Given via communication
● 6: Given by multi-speed
This parameter is similar to [b1.00], please see descriptions in [b1.00].
Bosch Rexroth AG
Parameter Settings
65/235