Bosch Rexroth EFC 3600 Operating Instructions Manual page 82

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

Bosch Rexroth AG
Parameter Settings
Fig.8-19: Square V/F curve auto torque boost
S0.22
I*R boost factor
Setting range
0%~320%
Minimum unit
1%
Factory default
100%
Used for further adjustment of the voltage boost. Its default value is 100 % which
means no adjustment is needed. The formula is shown as below:
Fig.8-20: Voltage boost
R
: stator resistance
1
I
: stator current
1
Thus, R
should be preset or calculated or tuned, and then input to [S2.10].
1
S0.24
Heavy load voltage stabilization
Setting range
0: disable; 1: enable
Minimum unit
1
Factory default
1
Used to depress the fluctuations in output voltage and current, which are caused by
bigger impact to DC bus voltage in case of heavy load.
80/235
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600