Ensuring The Emc Requirements - Bosch Rexroth EFC 3600 Operating Instructions Manual

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

Bosch Rexroth AG
Electromagnetic Compatibility (EMC)
According to IEC 61800-3, components of EFC 3600 drive system are
products of
● category C3: with internal EMC filter
● category C1: with external EMC filter
EFC 3600 frequency converter with internal EMC filter is applicable to
industrial environment (category C3). With installation of an external EMC
filter, EFC 3600 can fulfill C1 requirements.
WARNING
In a domestic environment (category C1) EFC 3600 frequency converter with internal
EMC filter may cause radio interference in which case supplementary mitigation
measures may be required.
See the following chapters for the limit classes (as per categories C1, C2, C3, C4
according to EN 61800-3) which can be reached for Bosch Rexroth Frequency
Converter EFC 3600.
11.2

Ensuring the EMC Requirements

Standards and laws
On the European level there are the EU Directives. In the EU states these Directives
are transformed into laws valid on a national level. The relevant directive for EMC is EU
Directive 2004/108/EC which was transformed on the national level in Germany into the
law EMVG ("Law concerning electromagnetic compatibility of devices") of 2008-02-26.
EMC Properties of Components
Drive and control components by Rexroth are designed and built, in accordance with
the present state-of-the-art of standardization, according to legal regulations of the EU
Directive EMC 2004/108/EC and the German law.
The compliance with EMC standards was tested by means of a typical arrangement
with a test setup conforming to standard with the indicated internal and external EMC
filters.
● Category C3 requirements according to product standard EN 61800-3 have been
complied with for EFC 3600 with an internal EMC filter.
● Category C1 requirements according to product standard EN 61800-3 have been
complied with for EFC 3600 with an external EMC filter.
● Minimum immunity requirements in the second environment according to product
standard EN 61800-3 have been complied with for EFC 3600 with internal and exter‐
nal EMC filters.