Bosch Rexroth AG
Parameter Settings
Fig.8-44: Stall overcurrent prevention level_during acceleration
At constant speed
● When the output current exceeds the stall prevention level set in [E4.03], the fre‐
quency converter starts deceleration with the defined deceleration time.
● When the output current drops below the value of [E4.03], the frequency converter
accelerates to the set frequency with the defined acceleration time.
Fig.8-45: Stall overcurrent prevention level_at constant speed
E4.04
Low speed derating frequency
Setting range
0.10 ~ 300.00 Hz
Minimum unit
0.01 Hz
Factory default
25.00 Hz
E4.05
Zero speed load
Setting range
25.0 % ~ 100.0 %
118/235
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600