Parameter Settings
Frequency source
Other setting sources in
[b1.00] and [b1.16]
b1.12~b1.14
Reserved
b1.15
Combination frequency command source
Setting range
0 ~ 2
Minimum unit
1
Factory default
0
● 0: no combination
● 1: first frequency setting + second frequency setting
● 2: first frequency setting - second frequency setting
EFC 3600 has two frequency setting sources: the first frequency setting source [b1.00]
and the second frequency setting source [b1.16]. It is allowed to use any of the fre‐
quency command sources or the combination of them.
● When the combination of two sources is active:
The reference and calculation of each part of the combination follows the rules and
definitions when it is used as a single command source input. Each part of the com‐
bination has the full frequency range, which means that the combined frequency
may theoretically become smaller than 0.00 Hz (when [b1.15] is set to 2]) or larger
than [b1.06] (when [b1.15] is set to 1). So the combined frequency is limited to the
range of 0.00 Hz ~ [b1.06].
64/235
RUN / STOP command
source
Panel
2-wire / 3-wire running control
[E0.00]
Communication
DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Direction command source
Defined by [b1.11]
2-wire / 3-wire running control
[E0.00]
Communication