Bosch Rexroth EFC 3600 Operating Instructions Manual page 69

Frequency converter
Hide thumbs Also See for Rexroth EFC 3600:
Table of Contents

Advertisement

DOK-RCON03-EFC-3600***-IT01-EN-P
Rexroth Frequency Converter EFC 3600
Factory default
0
b1.23
S curve starting phase proportion
Setting range
0.0 % ~ 40.0 %
Minimum unit
0.1 %
Factory default
20.0 %
b1.24
S curve stopping phase proportion
Setting range
0.0 % ~ 40.0 %
Minimum unit
0.1 %
Factory default
20.0 %
Used to set the acceleration / deceleration mode of the frequency converter to linear
curve or S-curve in start, stop, forward / reverse, acceleration / deceleration processes.
● [b1.22]=0: Linear mode
The output frequency is increased or decreased in linear as shown in figure below.
Fig.8-6: Linear mode
● [b1.22]=1: S-curve
The output frequency is increased or decreased in an S-curve (the S-curve mode is
used to achieve smooth start or stop) as shown in figure below.
Bosch Rexroth AG
Parameter Settings
67/235

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents