Action
"Access"
Scroll to menu H2.
"A"
Scroll to menu B11.
"A"
"A"
"Return"
"Return"
Rev: -
Disable / re-enable alert annunciation
function (H2/B11)
Normal operation:
For alarm points / zones programmed for Alert Annunciation (via
EBLWin) is normally the AA function enabled via a time channel, e.g.
enabled daytime (during working hours) and disabled night time.
As an alternative, the AA function can be continuously enabled.
Turned Off
Via this menu (H2/B11) it is possible to disable the AA function, i.e.
the AA function will be disabled for the alarm points / zones
programmed for Alert Annunciation in spite of the time channel is
"on" or if they are programmed to be continuously enabled.
The AA function will stay disabled until re-enabled again via this
menu.
Text in display
Disable or re-enable
Disable zone
Disable / re-enable alert annunciation
function
Alert annunciation function is in normal
operation.
Press ACCEPT to turn off
Alert annunciation function turned off.
Press ACCEPT to set to normal
Disable / re-enable alert annunciation
function
Disable or re-enable
NOTE! Disabled Alert Annunciation function is not indicated by
LED "Disablements" (L8).
The LED "Fault / Disablements Fire brigade tx delay" (L16) turned
off, is indicating that the Alert Annunciation function is turned off by
a time channel or is disabled via this menu.
EBL128 Operating Instructions V2.0.x
ACCEPT? H2
ACCEPT? B1
ACCEPT? B11
ACCEPT? B11
ACCEPT? H2
98
Comments
According to chapter
"Access", see page 81.
Depending on the actual
status one of the texts will
be shown.
Scroll or press "Return" to
menu H2.
Scroll or press "Return".